Mechanical installation

Important notes

3

l

73

EDKCSCE040 DE/EN/FR 3.0

3

Mechanical installation

3.1

Important notes

ƒ

ECS power supply modules are provided with IP20 enclosure and can
therefore only be used for installation in control cabinets.

ƒ

If the cooling air contains air pollutants (dust, fluff, grease, aggressive
gases):

–

Take suitable preventive measures , e.g. separate air duct, installation
of filters, regular cleaning.

ƒ

Possible mounting positions

–

Vertical at the mounting plate

–

DC bus connections (X22) at the top

–

Mains connection (X21) at the bottom

ƒ

Maintain the specified clearances (above and below) to other
installations!

–

If the ECSZS000X0B shield mounting kit is used, an additional clearance
is required.

–

Ensure unimpeded ventilation of cooling air and outlet of exhaust air.

–

Several modules of the ECS series can be installed in the control cabinet
next to each other without any clearance.

ƒ

The mounting plate of the control cabinet

–

must be electrically conductive.

–

must not be varnished.

ƒ

In case of continuous vibrations or shocks use shock absorbers.