Electrical installation

Power terminals

Mains connection

4

l

87

EDKCSCE040 DE/EN/FR 3.0

Fuses
Use the following circuit−breakers or UL−approved fuses to protect the mains
cable (see Fig. 4−2 (

86)):

Power supply

module

Dimensioning according to IEC/EN

Dimensioning to UL

Circuit−breaker

Cable

cross−section

[mm

2

]

UL fuse

AWG

ECSxE012

C16 A

2.5

25A

12

ECSxE020

C16 A

2.5

25A

12

ECSxE040

: 4

C 40 A

10

1)

35 A

8

1)

‚/„: 3, 4

C 32 A

6

35 A

10

ƒ: 3

C 40 A

6

2)

35 A

10

2)

ƒ: 4

C 40 A

10

35 A

8

1) Cable without wire end ferrule or with pin−end connector
2) Cable length max. 30 cm

J

Warnings!

ƒ

Use UL−approved cables, fuses and fuse holders only.

ƒ

UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"

Replacing defective fuses

{

Danger!

Hazardous electrical voltage
Components can carry hazardous voltages up to 3 minutes after
power−off.
Possible consequences:

ƒ

Death or severe injuries when touching the device.

Protective measures:

ƒ

Replace fuses in the deenergised state only.
– Set controller inhibit (CINH) for all axis modules in DC−bus

operation and disconnect all power supply modules from the
mains.