Electrical installation

Power terminals

4

l

83

EDKCSCE040 DE/EN/FR 3.0

4.3

Power terminals

{

Danger!

Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event
of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor

diameter

³ 10 mm

2

or PE conductor must be connected twice)

(

Stop!

No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the maximally permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains
fluctuations and voltage peaks.

ƒ

All power connections are plug connections and are coded. The connector
set for the ECSZE000X0B power supply modules must be ordered
separately.

ƒ

Installation of cables acc. to EN 60204−1.

ƒ

The cables used must comply with the approvals required for the
respective application (e.g. VDE, UL, etc.).