SimpleServo 100/200 User Manual Rev 3.4

2. Fault Digital Output

On hardware revisions 1.06 and earlier:

TTL compatible OC output (5V logic). High when drive is at fault, low otherwise.

On hardware revision 1.07

TTL compatible output (5V logic). High when drive at fault or disabled, low otherwise.

3. Enabled digital input

This is a single-ended input, compatible with 5V TTL, open-collector sink output, and switch or relay

contacts. The input is referenced to drive logic common. These inputs are active low, i.e., connecting it to

drive logic common or supplying logic "0" referenced to drive logic common activates this input. For

connection guidelines see application note in Appendix A. See figure below for electrical diagram.

4. Analog reference input

IN+, IN- (TB2-4,TB2-5)

Analog differential input. This input will accept +/-10V single-ended voltage on IN+ or IN- input or +/-5V

differential voltage between IN+ and IN-. Both connections must be referenced to Analog Common

(TB2-2) of the drive. This input is used to control speed or torque of the motor in velocity or torque

mode. The total reference voltage as seen by the drive is the voltage difference between IN+ and IN-. If

used in single-ended mode one of the inputs must be connected to voltage source while the other one

must be connected to Analog Common. If used in differential mode, the voltage source is connected

across IN+ and IN- inputs and driving circuit common (if any) needs to be connected to drive Analog

Common terminal.

Reference as seen by drive: Vref = (VIN+) - (VIN-)

Example #1:

Vin+ = 2V

Vin- =0 (connected to analog ground)

Vref = (2V) - (0V) = 2V (as seen by drive)

Example #2:

Vin+ = 2V

Vin- = -1V

Vref= (2V) - (-1V) = 3V (as seen by drive)


Example #3:

Vin+ = 2V

Vin- = 1V

Vref = (2V) - (1V) = 1V (as seen by drive)