3 omitted parameters and selections, 4 modified parameters and selections, Omitted parameters and selections – Lenze MCH Series Drives User Manual

Page 12: Modified parameters and selections, Drive setup & programming

Advertising
background image

9

RG-MHLON

Drive Setup & Programming

3.3 Omitted Parameters and Selections

36 SLEEP THRESHOLD

Sleep Mode functionality has not been added to the MCH Series LonWorks®
drive so these drive parameters do not exist.

37 SLEEP DELAY
38 SLEEP BANDWIDTH
41 ANALOG INPUT FILTER

52 TB14 OUT

The following options have not been added to these parameters in the MCH
Series LonWorks® drive:

53 TB15 OUT
54 RELAY

INV MIN/MAX A
MIN ALARM
INV MIN ALARM
MAX ALARM
INV MAX ALARM

58 SERIAL ADDRESS

The ABS_LON module only communicates with one MCH Drive so there is

no need for the drive to have a unique serial address and this parameter has
been removed.

3.4 Modified Parameters and Selections

8 ACCEL

This parameter defines the time that it will take for the drive to ramp the motor up
from 0.00Hz to Drive Parameter #11 (Max Frequency).

9 DECEL

This parameter defines the time that it will take for the drive to ramp the motor down
from Drive Parameter #11 (Max Frequency) to 0.00Hz.

24 AUTO SOURCE

The default selection for this parameter is KEYPAD. This setting is required if the
drive speed is to be modified over the LonWorks® network.

32 HZ MULTIPLIER The default setting for this parameter is 30.00.

56 SERIAL LOSS

The selections for this parameter are FAULT (default) and PRESET#3. The functionality
of this parameter is described in Section 3.5 Serial Communications Setup.