Lonworks network variables – Lenze MCH Series Drives User Manual

Page 25

Advertising
background image

RG-MHLON

22

LonWorks Network Variables

nciStopMode

Definition

Network config input SNVT_switch nciStopMode

Explanation

This input network variable is used to choose between coast and ramp stop.

Valid Range:

State

Value

Command

0

0.0%

Coast to stop

1

100.0%

Ramp to stop

Default Value 0

nciStopLevel

Definition

Network config input SNVT_lev_percent nciStopLevel

Explanation

This is the stop level for the drive when it is in ramp to stop mode. When the drive
is ramping to a stop and reaches this level, a coast to stop is performed. The value
is relative to nvoDrvSpeed ( i.e. a value of 5% corresponds to a nvoDrvSpeed value
of 5%).

Valid Range

-163.840% to 0.00 % or 0.00% to +163.835%

The value 0x7FFF represents invalid data.

Default Value 5.000 %

nciParValue

Definition

Network config input SNVT_count_inc nciParValue

Explanation

This nci is used as a value input for the user selected parameter nciParWrite.

Valid Range

1 - 46

Default Value 0

nciParRead

Definition

Network config input SNVT_count nciParRead

Explanation

Chooses the parameter value to be read from the drive.

Valid Range

1 - 46

Default Value 0