LonWorks Network Variables

NviDrvSpdScl

Definition

Network input SNVT_lev_percent nviDrvSpeedScale

Explanation

This input network variable provides scaling for nviDrvSpeedStpt (0.005%
resolution).

For example, if the value of nviDrvSpeedStpt is 100% and nviDrvSpdScl value
is 150%, then the actual speed setpoint value is 150% meaning that the drive
should run at 1.5 times nominal speed in the forward direction. A negative value
for nviDrvSpdScl sets the drive direction to reverse.

For example if nviDrvSpeedStpt value is 100% and nviDrvSpdScl value is -150%,
then actual speed setpoint value is -150%, meaning that he drive should run at
1.5 times nominal speed in the reverse direction.

Valid Range

-163.840% to 0.00 % or 0.00% to +163.835%

The value 0x7FFF represents invalid data.

Default Value Defined by nciDrvSpdScl.

NviResetFault

Definition

Network input SNVT_switch nviResetFault

Explanation

This input network variable provides a mechanism to clear a fault status in the
drive.

Valid Range:

State

Value

Command

0

0.0%

Reset Fault Ready

1

100.0%

Reset Fault

On a transition from 0 to 1, this input network variable clears the fault condition in the drive.

Following a fault reset, this variable must be set back to 0 to enable the next fault
reset.

Default Value The drive will power-up in the ‘Reset Fault Ready’ state.