Electrical installation, Stop – Lenze EPM−H502 User Manual

Page 67

Advertising
background image

Electrical installation

Wiring of the system bus (CAN)

4

l

67

EDBPM−H502 DE/EN/FR 5.1

Connection

FUSE 800 mA

+(18-32) VDC 10W

0 VDC

1

2

3

4

N. C.

12

3

4

ASP8

N.C.

CAN+

Shield

CAN-

V-

1 2 3 4 5

CAN-GND

CAN-LO

CAN-HI

h502_012

Fig. 4−3

System bus (CAN) connection

Terminal assignment

(

Stop!

Connect a 120

W terminating resistor to the first and last bus device.

Terminal

Identification

Explanation

1

V−

GND

Reference potential

2

CAN−

LO

System bus LOW (data line)

3

Shield

Connect the shield of the system bus cable

4

CAN+

HI

System bus HIGH (data line)

5

n.c.

Not connected

For the use of the transmission cable, follow our recommendations:

Specification of the transmission cable

Total length

£ 300 m

£ 1000 m

Cable type

LIYCY 2 x 2 x 0.5 mm2
(paired with shielding)

CYPIMF 2 x 2 x 0.5 mm

2

(paired with shielding)

Cable resistance

£ 80 W/km

£ 80 W/km

Capacitance per unit
length

£ 130 nF/km

£ 60 nF/km

Advertising