Electrical installation
Wiring of the system bus (CAN)
l
67
EDBPM−H502 DE/EN/FR 5.1
Connection
FUSE 800 mA
+(18-32) VDC 10W
0 VDC
1
2
3
4
N. C.
12
3
4
ASP8
N.C.
CAN+
Shield
CAN-
V-
1 2 3 4 5
CAN-GND
CAN-LO
CAN-HI
h502_012
Fig. 4−3
System bus (CAN) connection
Terminal assignment
(
Stop!
Connect a 120
W terminating resistor to the first and last bus device.
Terminal
Identification
Explanation
1
V−
GND
Reference potential
2
CAN−
LO
System bus LOW (data line)
3
Shield
Connect the shield of the system bus cable
4
CAN+
HI
System bus HIGH (data line)
5
n.c.
Not connected
For the use of the transmission cable, follow our recommendations:
Specification of the transmission cable
Total length
£ 300 m
£ 1000 m
Cable type
LIYCY 2 x 2 x 0.5 mm2
(paired with shielding)
CYPIMF 2 x 2 x 0.5 mm
2
(paired with shielding)
Cable resistance
£ 80 W/km
£ 80 W/km
Capacitance per unit
length
£ 130 nF/km
£ 60 nF/km