7 troubleshooting and fault elimination, 1 fault messages, Troubleshooting and fault elimination – Lenze EPM−H502 User Manual

Page 84: Fault messages, 7troubleshooting and fault elimination

Advertising
background image

Troubleshooting and fault elimination

Fault messages

7

l

84

EDBPM−H502 DE/EN/FR 5.1

7

Troubleshooting and fault elimination

7.1

Fault messages

Call up the status messages of the operating unit to display the fault message
that occurred last. (

73)

Display

Fault

Cause

Remedy

NO ERROR

No fault

PR ERROR

Faulty data
exchange

Connection between operating
unit and PC is faulty

l

Check that the connections are
firmly seated.

l

Check cable for damages

COM BROK

Communication
interrupted

Serial data cable between
operating unit and PC is
defective or not correctly
connected

l

Check Sub−D connector for correct
connection and firm seating.

l

Replace serial data cable

ASIC ko1

Communication
with system
bus (CAN)
interrupted

l

Faulty wiring (e. g. polarity)
of the system bus

l

Faulty parameterisation of
interface (baud rate,
address, identifier)

l

Check wiring of system bus (CAN)
(

^

66)

l

Check parameter setting (

^

HMI

Designer − Getting started).

ASIC ko2
ASIC ko3
ASIC ko4
RESET
SDOERR 6
SDOERR 5
SDOERR 3

Advertising