Electrical installation

Wire system bus (CAN)

4



64

EDBPM-H521 DE/EN/FR 2.0

4.2

Wire system bus (CAN)

Note!

ƒ

Only connect terminals of the same signal type.

ƒ

For further information with regard to the system bus (CAN) please

refer to the CAN Communication Manual.

Shield

CAN-

-V

CAN+ N.C.

CG LO HI

CG LO

CG LO HI

CG LO HI

HI

120

120

A

n

A

2

(H521)

A

1

h521_009

Fig.4-2

Wiring of system bus (CAN)
A

1

Bus node 1

A

2

Bus node 2

A

n

Bus node n

Please observe our recommendations for signal cables:

Specification for the transmission cable
Total length

≤ 300 m

≤ 1000 m

Cable type

LIYCY 2 x 2 x 0.5 mm

2

(twisted in pairs with shield)

CYPIMF 2 x 2 x 0.5 mm

2

(twisted in pairs with shield)

Cable resistance

≤ 80 Ω/km

≤ 80 Ω/km

Capacitance per unit

length

≤ 130 nF/km

≤ 60 nF/km