7 troubleshooting and fault elimination, 1 fault messages, Troubleshooting and fault elimination – Lenze EPM-H521 User Manual

Page 86: Fault messages, 7troubleshooting and fault elimination

Advertising
background image

Troubleshooting and fault elimination

Fault messages

7



86

EDBPM-H521 DE/EN/FR 2.0

7

Troubleshooting and fault elimination

7.1

Fault messages
Call up the status messages of the operating unit to indicate the last occurred fault

message. (Q 71)

Display

Fault

Cause

Remedy

NO ERROR

No fault

-

-

PR ERROR

Faulty data

exchange

Connection between operating

unit and PC is faulty

Check connections for tight fit

Check cable for damages

COM BROK

Communication

interrupted

Serial data cable between

operating unit and PC is

defective or not correctly

connected

Check correct connection and tight fit

of Sub-D plug

Exchange serial data cable

ASI

ko1

Communication

Faulty wiring (e g polarity) of

Check wiring of system bus (CAN)

ASIC ko1

Communication

ith

t

Faulty wiring (e. g. polarity) of

th

t

b

Check wiring of system bus (CAN)

(

E

64)

ASIC ko2

with system

bus (CAN)

y

g ( g p

y)

the system bus

Faulty parameter setting of

g

y

(

)

(

E

64)

Check parameter setting (

E

HMI

ASIC ko3

bus (CAN)

interrupted

Faulty parameter setting of

interface (baud rate, address,

Check parameter setting (

E

HMI

Designer - Getting started).

ASIC ko4

interrupted

interface (baud rate, address,

identifier)

Designer - Getting started).

RESET

de t e )

SDOERR 6

SDOERR 5

SDOERR 3