Drive control & communication – Lenze TCF Series Drives Modbus Communications User Manual

Page 18

Advertising
background image

RG-TFMOD 14

Drive Control & Communication

5.4.2 Operational Status - Registers #24 & 26

Table 10 lists the Operational Status (Register #24 byte D3L or Register #26 DL)

Table 10: Operational Status

Setting

Parameter

0

FAULT LOCKOUT

1

FAULT

2

START PENDING

3

STOP

4

DC BRAKE

5

RUN AT 0Hz

6

RUN

7

ACCEL

8

DECEL

9

CURRENT LIMIT

10

DECEL OVERRIDE

11

LOWER TRANSISTORS SWITCHING ON

5.4.3 Actual Rotational Direction - Registers #24 & 27

Table 11 lists the Actual Rotational Direction (Register #24 byte D4H or Register #27 DH).

Table 11: Actual Rotational Direction

Setting

Direction

0

FORWARD

1

REVERSE

5.4.4 Control Mode - Registers #24 & 27

Table 12 lists the Control Mode (Register #24 byte D4L or Register #27 DL).

Table 12: Control Mode

Setting

Control

Operation

0

TERMINAL

Start/Stop operation controlled from the drive's terminal strip

1

REMOTE KEYPAD (Control)

Start/Stop operation controlled from remote keypad

2

REMOTE KEYPAD (Program)

Remote keypad used for drive programming;
Start/Stop operation controlled from the drive's terminal strip

3

SERIAL

Start/Stop operation controlled via serial link