23 RG-TFMOD

Drive Control & Communication

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

130 (82H)

80

Drive Mode

01 - Constant V/Hz
02 - Variable V/Hz
03 - Enhanced Constant V/Hz
04 - Enhanced Variable V/Hz
05 - Vector Speed
06 - Vector Torque

01 - Constant V/Hz

131 (83H)

81

Auto Calibration

00 - Calibration Not Done
01 - Calibration Cycle Enabled
02 - Calibration Complete

00 - Calibration Not Done

132 (84H)

82

Current Loop P Gain

0 - 1600 (0.00 - 16.00)

25 (0.25)

2

133 (85H)

83

Current Loop I Gain

120 - 9990 (12 - 999 msec)

650 (65 msec)

134 (86H)

84

Stator Resistance

0 - 6400 (0.00 - 64.00 ohms) refer to Note 8

0 (0.00 ohms)

2

135 (87H)

85

Motor Rated Speed

3000 - 650000 (300 - 65000 RPM)

17500 (1750 RPM)

136 (88H)

86

Motor Rated Amps

0 - 480 (0.0 - 48.0 amps)

0 (0.0 amps)

137 (89H)

87

Motor Rated Volts

0 - 6000 (0 - 600 VAC)

0 (0 VAC)

138 (8AH)

88

Motor Base Frequency

250 - 5000 (25 - 500 Hz)

600 (60 Hz)

141 (8DH)

91

Motor Cosine Phi

40 - 99 (0.40 - 0.99)

90 (0.90)

2

142 (8EH)

92

Motor Inductance

0 - 20000 (0.0 - 2000 mH) refer to Note 8

0 (0.0 mH)

143 (8FH)

93

Torque Limit

0 - 4000 (0 - 400 %)

1000 (100 %)

144 (90H)

94

Drive Personality

(Read Only) Refer to section 5.3 Drive Size

EPM copy of Drive Index

145 (91H)

95

Motor Current

(Read Only)

N/A

146 (92H)

96

Torque Percent

(Read Only)

N/A

1

= Drive's programming parameter number

2

= Two decimal places assumed (hundredths)

Advertising