Drive control & communication, 2 parameter list – Lenze TCF Series Drives Modbus Communications User Manual

Page 23

Advertising
background image

19 RG-TFMOD

Drive Control & Communication

6.2 Parameter List

AC Tech
Register
Number
(hexadecimal
representation)

Parameter

1

Parameter Name

Range of Adjustment
Modbus value (decimal value)

Factory Default

51 (33H)

01

Line Voltage

01 - High
02 - Low

01 - High

52 (34H)

02

Carrier Frequency

01 - 2 kHz
02 - 4 kHz
03 - 8 kHz

02 - 4 kHz

53 (35H)

03

Start Method

01 - Normal
02 - Start on Power-up
03 - Start w/DC Brake
04 - Auto Restart w/DC Brake
05 - Flying Restart 1
06 - Flying Restart 2

01 - Normal

54 (36H)

04

Stop Method

01 - Coast
02 - Coast with DC Brake
03 - Ramp
04 - Ramp with DC Brake

01 - Coast

55 (37H)

05

Standard Reference
Source

Speed Mode:
01 - Keypad
02 - Preset #1
03 - 0-10 VDC
04 - 4-20 mA

Torque Mode:
01 - Keypad
02 - Keypad
03 - 0-10 VDC
04 - 4-20 mA

01 - Keypad

56 (38H)

06

TB-14 OC Output

01 - None
02 - Run
03 - Fault
04 - Inverse Fault
05 - Fault Lockout
06 - At Set Speed
07 - Above Preset #3
08 - Current Limit
09 - Auto Speed (speed source via terminal strip)
10 - Reverse (rotation direction indication)
11 - Dynamic Braking

01 - None

57 (39H)

07

Bipolar Reference

01 - Disable
02 - Enable

01 - Disable

58 (3AH)

08

TB-30 Analog Output

01 - None
02 - 0-10 VDC Freq
03 - 2-10 VDC Freq
04 - 0-10 VDC %Load
05 - 2-10 VDC %Load
06 - 0-10 VDC Torque
07 - 2-10 VDC Torque

01 - None

1

= Drive's programming parameter number

Advertising