5 step 2: parameterising the application – Lenze E94AxHE Technology Application Positioning sequence control User Manual
Page 17

EDS94TA10060xxxx EN 1.2 - 03/2010
L
17
9400 Technology applications | Positioning sequence control
Short setup
Step 2: Parameterising the application
4.5
Step 2: Parameterising the application
For parameterising the application in the »Engineer«, use the Application parameters tab
which will be displayed by default when selecting the controller in the project view:
1. Select the mains voltage (C00173).
2. Activate automatic brake control via brake module (C02580 = "Autom. with brake
module").
3. Enter gearbox ratio as a quotient (numerator and denominator): i
1
= 12.612 = 12612/
1000
– Numerator (C02520) = 12612
– Denominator (C02521) = 1000
4. Select "Unlimited" as traversing range (C02528).
5. Click Machine parameter to change to the dialog level Overview Machine parameter
for further parameter setting.