RKI Instruments Pioneer 16R User Manual

Page 12

Advertising
background image

relay is factory-set for normally energized and is not user-selectable.

Alarm 1 Condition

This section describes the audible and visual indications for an alarm 1 condition and suggests response
to an alarm 1 condition.

Alarm 1 condition indications
When the gas reading of an active channel reaches the alarm 1 setpoint, the Pioneer senses an alarm
1 condition. The Pioneer alerts you to an alarm 1 condition as follows:
-

The ALARM 1 light turns on

-

The gas reading in alarm 1 condition flashes

-

The buzzer sounds a pulsing tone

-

The common alarm 1 relay energizes

-

The alarm 1 relay on the applicable analyzer card energizes

Responding to an alarm 1 condition
-

Follow your established procedure for a low level combustible or toxic gas condition or a
decreasing oxygen content condition.

-

After the gas reading falls below the alarm 1 setpoint, press the reset switch to reset the alarm 1
circuit. Resetting the alarm 1 circuit silences the buzzer, turns off the ALARM 1 light, and de-
energizes the common and analyzer card alarm 1 relays.

N O T E

:To silence the buzzer while in an alarm 1 condition, press the reset switch. You cannot de-

energize the alarm 1 relays until the gas reading falls below (above for oxygen) the alarm 1
setpoint.

Alarm 2 Condition

This section describes the audible and visual indications for an alarm 2 condition and suggests response
to an alarm 2 condition.

Alarm 2 condition indications
When the gas reading of an active channel reaches the alarm 2 setpoint, the Pioneer senses an alarm
2 condition. The Pioneer alerts you to an alarm 2 condition as follows:
-

The ALARM 2 light turns on

-

The gas reading in alarm 2 condition continues to flash

-

The buzzer sounds a faster pulsing tone than an alarm 1 condition

-

The common alarm 2 relay energizes

-

The alarm 2 relay on the applicable analyzer card energizes

Responding to an alarm 2 condition
This section suggests response to an alarm 2 condition.
-

Follow your established procedure for a mid level combustible or toxic gas condition or a severe
decreasing oxygen content condition.

-

After the gas reading falls below the alarm 2 setpoint, press the reset switch to reset the alarm
circuit. Resetting the alarm circuit turns off the ALARM 2 light, and de-energizes the common and
analyzer card alarm 2 relays.

N O T E

:To silence the buzzer while in an alarm 2 condition, press the reset switch. You cannot de-

energize the alarm 2 relays until the gas reading falls below (above for oxygen) the alarm 2
setpoint.

Alarm 3 Condition

This section describes the audible and visual indications for an alarm 3 condition and suggests response
to an alarm 3 condition.

Alarm 3 condition indications

Pioneer-R16 Operator’s Manual

Operation

11