P40U-F / P40U-IF I&O Manual

IM101220

RD: MAY 2014

RL: 5A

For 30° angle mount: Remove burner (4 bolts + spark wire); Install the tube system; Reinstall
burner to flange using appropriate holes to maintain horizontal orientation of burner.

Use all four suspension points + a chain at burner eye hook.
Hardware capable of supporting minimum 100 lbs (45 kg)
at each suspension point.
For seismic and high wind restraint see
Sections 8-A & 8-B.

FIGURE 4 TYPICAL SUSPENSION

72

(1

83

cm

)

SERVICE ACCESS: ALLOW A MINIMUM OF
6 INCHES (15 cm) FROM THE ACCESS END
OF THE BURNER AND A MINIMUM OF 24
INCHES (60 cm) FROM EITHER SIDE OF
THE BURNER TO A WALL OR ANY OB-
STRUCTION THAT WOULD RESTRICT OR
LIMIT ACCESS TO THE BURNER (SEE
SECTIONS 5 & 6 - PRE-INSTALLATION
SURVEY AND MOUNTING CLEARANCES)

Connect to properly
grounded 120V
power supply

FIGURE 5 HEATER DIMENSIONS & SUSPENSION ANGLE OPTIONS

Burner always

horizontal

Vent side

always upper

Turbulators (factory installed): Burner side tube: 36” (914 mm)

.

Vent side tube: 90” (2286 mm)