Schwank P40U Fenwal User Manual

Page 18

Advertising
background image

18

P40U-F / P40U-IF I&O Manual

IM101220

RD: MAY 2014

RL: 5A

H

ORIZONTAL

VENT

THROUGH

A

SIDE

WALL

:



Maximum allowable flue vent length is equivalent to 20 feet [6.1 m]



A maximum of two 90°elbows (each equivalent 5 ft [1.5 m]) can be installed in the vent



The flue vent system must slope downwards approximately 1/4" per foot (63 mm / 300 mm)
toward the vent terminal, from the termination of the tube - radiant tube must be level.

continued ……..

’B’ Vent
Through
Wall

18” Min.

These minimum clearance

apply when using the

following Vent Terminal

4” (10 cm) - JA-0528-XX

or

6” (15 cm) - JA-0529-XX

See notes below

for use of other

approved vent terminations

FIGURE 10 - Horizontal Vent - ALL vent pipe and adapters by others

need to be equidistant to the vent Tee, but must comply to requirements below. The two
heaters must be controlled by a single common thermostat or “ON/OFF” switch.



A minimum 12 inch (30 cm) length of minimum 26 gauge single walled 4” (10 cm) diameter
vent pipe is to be installed on the swaged end of the tube before any Tee or Elbow is fitted.



Seal all vent connections with high temperature sealant. Vent connections must be secured
with three (3) #8 sheet metal screws uniformly spaced around the circumference of the
vent pipe.



When the vent pipe passes through a cold or unheated area where the ambient tempera-
ture is likely to produce condensation of the flue gases, the vent pipe will be insulated with
a suitable material as approved and specified by the insulation manufacturer to withstand
temperature up to 460°F (238°C).



The vent system must always be adequately supported to prevent sagging.

Single wall vent
from heater

‘C’ to ‘B’
adapter

Combustible Overhang

6”

Min.

FIGURE 9 - Heater Expansion - Suggested Vent Configuration*

By Others

All Vent Pipe & Adapters

By Others

* Other means of slip fit
installation of the vent
and duct are acceptable
providing there is ade-
quate allowance for free
expansion and contrac-
tion of the system, and
free flow of vent gases
and combustion air.

Advertising