P40U-F / P40U-IF I&O Manual

IM101220

RD: MAY 2014

RL: 5A

24. TROUBLESHOOTING GUIDE — HEATER OPERATION — FENWAL DSI

Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
installed and serviced only by a trained gas service technician

SET THERMOSTAT TO CALL FOR

APPLY 120 VOLTS - GREEN LIGHT



CHECK 120V TO DSI AT “L1”



CHECK 120V OUT AT “IND” FROM DSI TO

COMBUSTION AIR BLOWER

AIR PROVING SWITCH HAS

CLOSED 24 VOLTS IS PRESENT

AT “PSW” AT DSI CONTROL.



CHECK TUBING TO SWITCH IS CON-
NECTED AND NOT BLOCKED OR KINKED



CHECK AIR PRESSURE WITH MANOME-
TER



CHECK FOR OBSTRUCTION IN THE AIR
INTAKE



CHECK DSI CONTROL FUSE FOR CONTI-
NUITY



VISIBLY CHECK IF IGNITER IS SHORTING
OUT



CHECK GROUND WIRING



REMOVE AND INSPECT IGNITER AND
LEAD



CHECK BOOT OF THE IGNITION CABLE
FOR SIGNS OF MELTING OR OVERHEAT-
ING



IF “YES” ... TAKE PROTECTIVE ACTION TO
SHIELD CABLE AND BOOT FROM EXCES-
SIVE TEMPERATURE; REPLACE ANY DE-
FECTIVE COMPONENT

SPARK IGNITER / SENSOR

24V TO GAS VALVE - RED LIGHT

CONTINUED

SEQUENCE OF EVENTS (also see DSI Troubleshooting previous page)

NO

YES

YES

YES

NO

NO



REMEDY 120 VOLTS SUPPLY FAULT

NO

NO



FAULTY RELAY SWITCH IN DSI — RE-
PLACE DSI

BLOCKED FLUE SWITCH IS

CLOSED

24 VOLTS IS PRESENT AT “TH” AT

YES

NO



CHECK TUBING TO SWITCH IS CON-
NECTED AND NOT BLOCKED OR KINKED



CHECK AIR PRESSURE WITH MANOME-
TER



CHECK INTEGRITY OF SWITCH



REPLACE DEFECTIVE SWITCH

WARNING