P40U-F / P40U-IF I&O Manual

IM101220

RD: MAY 2014

RL: 5A

FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* - Table 1 lists values

*The clearance to combustible materials represents the minimum distance that must be main-

tained between the heater and a nearby surface. The stated clearance to combustibles
represents a surface temperature of 90F° (50C°) above room temperature.

NOTE: A ‘PEEL & STICK’ SIGN IS SUPPLIED: USE AN INDELIBLE MARKER TO

ENTER VALUES ON THE SIGN: ‘H’ = Calculate (instruction below)

Sides of horizontal heater: ‘S’ = 24 inches (61 cm)

Front of 30° Angle heater: ‘F’ = 36 inches (91.5 cm)

Behind 30° Angle Heater ‘B’ = 24 inches (61 cm)

POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A
PROMINENT LOCATION.

See next page for details.

TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLE SURFACES OR MATERIALS*

MODELS

SUSPENDED
HORIZONTALLY

SUSPENDED AT AN ANGLE
UP TO 30 DEGREES

P40U / P40U-I
P40U-P / P40U-IP
P40U-W

/

P40U-IW

TOP

inches (cm)

BELOW

inches (cm)

SIDES

inches (cm)

TOP

inches (cm)

BELOW

inches (cm)

FRONT

inches (cm)

BEHIND

inches (cm)

12

(30.5) 55 (140) 24 (61)

12

(30.5) 55 (140)

36 (91.5)

12

(30.5)

Clearance from ‘U’ end of heater (horizontal or angled): 24”

(61 cm)

Calculate Maximum Stack Height ‘H’: (Enter value ‘H’ on the peel and stick label supplied)



H = T- 55 inches (140 cm)



‘T’ is measured on site = distance from the bottom of the heater hanger to the floor



55 inches (140 cm) is the required minimum clearance below the heater

H

Suspended at
an angle of 30°

Suspended
horizontally

T

FLOOR

T

FLOOR

H

24” (61 CM) FROM ‘U’ TUBE

END OF HEATER