Warning – Schwank P40U Fenwal User Manual

Page 8

Advertising
background image

8

P40U-F / P40U-IF I&O Manual

IM101220

RD: MAY 2014

RL: 5A

VENT END CLEARANCE: Clearances from the vent pipe are determined by local or national
installation codes, but must not be less than 6 inches (15 cm). For ‘unvented’ installation, a
minimum distance of 24 inches (61 cm) is required from the end of heater to a combustible
surface.


In locations used for the storage of combustible materials:
Signs must be posted
specifying the maximum permissible

stacking height to maintain the required clearances from the heater to the combustibles.

The signs must be posted either adjacent to the IR heating system thermostats or in the ab-

sence of such thermostats, in a conspicuous place.

For your convenience a “peel and stick” sign
is provided with this heater. Use a permanent
marker to record the required dimensions on
the sign.

H’ is a value calculated at site: (H = T - C)
 Measure the on site distance between bottom of

the hanger and the floor = ‘T’ inches (cm).

 The minimum clearance to combustibles below

this model heater is 55 inches (140 cm)

 Subtract 55 inches (140 cm) from ‘T’ to get

value ‘H’.

 Enter the calculated value ‘H’ on the sign

For model P40U enter the values for other dimen-

sions are: ‘S’ = 24” (61 cm), ‘F’= 36” (91.5 cm) and

B’ = 12” (30.5 cm). See Figure 1 and Table 1

Post this sign as instructed above.

It is the installer’s responsibility to ensure that building materials with a low heat toler-
ance which may degrade at lower temperatures are protected to prevent degradation.
Examples of low heat tolerance materials include vinyl siding, fabrics, some plastics,
filmy materials, some coatings and laminated finishes, etc.

24”

12”

36”

WARNING