26. HIGH ALTITUDE INSTALLATION

Canada: Heaters can be installed to an altitude of 4500 ft without revision

.



To install above 4500 feet refer to recommendation of local authority having jurisdiction.

USA: The factory installed orifice is approved for normal altitude up to 2000 ft.

When this appliance is installed above an altitude of 2000 feet in the USA , the input must be

de-rated by 4% for each 1000 ft . Refer to the table next page for orifice sizing and restrictions

that apply to high altitude installation. Check with your local authority regarding de-rating.

NOTE: Installations above 4,500 ft: Restrict the Total Combined System Length as indi-
cated in the TOTAL SYSTEM LENGTH RESTRICTIONS Table below.

MINIMUM VENT LENGTH: (Vented or Unvented [indirect mechanical ventilation])



Minimum vent length of 3 ft (91 cm) is required (

NOTE: 200,000 LP: Minimum 8 ft (244 cm)

MAXIMUM SYSTEM LENGTH (includes:

Tube Heater length + combustion air duct + vent

):



Each 90° elbow in the system has an equivalent length of 5 ft.



A maximum of 2 elbows are allowed in any portion (duct, tube heater, vent) with the ex-
ception of up to three 90° elbows in a vertical vent run through the roof



Combustion air duct may be 4” or 5” diameter and is not to exceed lengths in table below

 Exceeding the allowable lengths in the table below can create combustion and/or conden-

sation problems and will void CSA Certification and the heater warranty.

 Do not exceed the Maximum Combined System Length regardless of the allowed maxi-

mum length of individual vent or combustion air duct

Input

(Btuh)

Do Not Exceed

Maximum Combined

System Length

Max. Air Duct

Length (ft)

(by Duct Diameter)

Max. Vent

Length (ft)

Individual: 4ӯ

Combined: 6ӯ

4”

Air Duct 5” Air Duct

4”

Ш

5”

Ш

45,000

& 60,000

40 ft

60 ft

20 ft

40 ft

20 ft

80,000

50 ft

70 ft

20 ft

40 ft

20 ft

100,000

40 ft

60 ft

30 ft

50 ft

30 ft

110,000

to 150,000

80 ft

100 ft

30 ft

50 ft

30 ft

175,000

& 200,000

100 ft

120 ft

30 ft

50 ft

40 ft

Example

150,000 Btuh Heater:

Tube Heater Length 40 ft

1 x 90° elbow (vent)

5 ft

Straight vent

15 ft

1 x 90° elbow (duct)

5 ft

Air Duct: 4” Ø

13 ft

Combined Length

78 ft

Max. Allowed

80 ft

Additional 20’ for 5” Ø Air Duct

TOTAL SYSTEM LENGTH RESTRICTIONS:
INSTALLATIONS ABOVE 4500 FEET (
Lower altitudes refer to Section 12A)