S100-F / ITB-F I&O Manual

IM101230

RD: SEP 2014

RL: 11A

HONEYWELL S87J: WIRING DIAGRAM: 24 VOLT THERMOSTAT OPERATION

(120V Thermostat - previous page)

Maximum Power Flow = 21VA

Each tube heater requires 120V, 60 HZ electrical power sized for 145VA. The 24V/120V re-
lay switch shown above is an option (JS-0568-KT) that is field installed. Maximum power flow
for internal 24V burner components is 21VA.

The heater must be electrically grounded in accordance with the National Electrical Code.
ANSI / NFPA 70 or current Canadian Electrical code CSA C22.1.

A maximum night set-back of 9°F (5°C) is recommended for optimum economy and comfort.
To maintain satisfactory comfort levels do not turn off the heating system over night/weekends.

RELAY

Field installed option
Kit JS-0568-KT

OTHER DSI’s: FENWAL SEE PAGE 35; CHANNEL MICRO 50N - PAGES 62 - 65