P40R-F I&O Manual
IM120801
RD: MAY 2014
RL: 3A

For your convenience a “peel and stick” sign is provided

with this heater. Sign must be posted either adjacent to the

IR heating system thermostat or in the absence of such thermostat, in a conspicuous place
specifying the required clearances from the heater to the combustibles.

Use a permanent marker to record the required clearance dimensions on the sign.

H’ is a value calculated at site: (H = T - C) Refer to Figure 1 and Table 1 above
 Measure the on site distance between bottom of the heater and the floor = ‘T’ inches (cm).
 The minimum clearance to combustibles below this heater ‘C’ is 53 inches (1135 cm)
 Subtract ‘C’ 53 inches (135 cm) from ‘T’ (Height

above floor) to get value ‘H’.

 Enter the calculated value ‘H’ on the sign

Enter the values as required for the other dimen-

sions:

S’ = 24” (61 cm)

F’= 36” (91.5 cm)

B’ = 12” (30.5 cm) at 30°

Or ‘B’ = 24” if mount angle less than 30°

POST THIS SIGN ADJACENT TO THE HEATER
THERMOSTAT OR IN A PROMINENT LOCATION
.

24”

12”

36”

WARNING

VENT CLEARANCE: Clearance from single wall ’C’ vent pipe inside the building is deter-
mined by local or national installation codes, but must not be less than 6 inches (15 cm).

Clearance from the vent terminal outside the structure are indicated in Section 11 Flue Vent-
ing and Figures 9 to 12, pages 19 to 23 for details and requirements for venting.