FIGURE 11: LOCATION OF HORIZONTAL (SIDE WALL) VENT TERMINAL

Clearance required:

Canada

1

USA

2

Above grade, veranda, porch, deck, balcony

12” (30 cm)

12” (30 cm)

To a window or door that may be opened

12” (30 cm)

9” (23 cm)

To a permanently closed window

** **

Below a ventilated soffit within 2 ft horizontal from

center of terminal

12” (30 cm)

9” (23 cm)

Below an unventilated soffit

3” (7.6 cm)

3” (7.6 cm)

To an outside corner

12” (30 cm)

12” (30 cm)

To an inside corner

12” (30 cm)

12” (30 cm)

To each side of centerline extended above a
meter/regulator assembly

3 ft (91 cm) within 15 ft (4.5 m)
height above meter/regulator

**

To a service regulator vent outlet

3 ft (91 cm)

**

To non-mechanical air supply inlet or combustion

air inlet to other appliance

12” (30 cm)

9” (23 cm)

To mechanical air supply inlet

6 ft (1.83 m)

3 ft (91 cm) above
if within 10 ft (3

m)

horizontally

Above sidewalk or paved drive on public property

7 ft (2.13 m) †

**

A

B

C

D

E

F

G

H

I

J

K

L

M Under veranda, porch, deck, balcony

12” (30 cm) ‡

**

See Table footnotes previous page

TABLE 3