21

P40R-F I&O Manual

IM120801

RD: MAY 2014

RL: 3A

H

ORIZONTAL

VENT

THROUGH

A

SIDE

WALL

: (Vertical vent through roof is on page 23)



Refer to General Venting Requirements on page 19



Minimum length of a horizontal side-wall vent:



Regardless if a 90° elbow is installed, a Minimum linear 36 inch (3 ft; 91 cm) single
wall ‘C’ vent plus minimum 12 inch (30.5 cm) double wall ‘B’ vent through wall



Total minimum linear vent length of 48 inches (4 ft; 122 cm)



Maximum length of a horizontal side-wall vent:



Total Maximum vent length is 15 ft (4.6 m)



Each 90° or 45° elbow is equivalent to 5 ft



A minimum 12 inch (30.5 cm) double wall ‘B’ vent must be used through the wall



The flue vent system must slope downwards approximately 1/4" per foot (63 mm / 300 mm)
toward the vent terminal, from the termination of the tube - radiant tube must be level.



A maximum of two elbows (90° or 45°; each = equivalent 5 ft) can be installed in a horizon-
tal vent



For side wall venting use either Schwank/InfraSave 4”

(10 cm) horizontal vent terminal (Part

Number: JA-0528-XX - available as an option) or an approved 4”

(10 cm) “High Wind” vent

termination cap (see clearance information previous page and next page)



Install the termination cap a minimum of 6 inches (15 cm) from the outside wall to the inside
edge of terminal opening to minimize back pressure caused by turbulent wind conditions
(See Fig. 9 above). This also ensures flue gases are directed away from the structure to
help protect building materials from degradation by the exhausted flue gases.



The vent must be installed to prevent blockage by snow, undue wind pressure on the termi-
nation, and to protect building materials from degradation by flue gases.

Clearances Required for Horizontal Side Wall Vent :



Refer to Figure 9 above, and in particular to Figure 11 and Table 3 next page for specific
requirements of codes in the USA and Canada



Any values not listed in Table 3 shall be in accordance with local installation codes and the
requirements of the gas supplier

Footnotes for Table 3 (next page)

1

Installations in Canada in accordance with current CSA B149.1, Natural Gas and Propane

installation Code

2

Installations in the USA in accordance with the current ANSI Z223.1 / NFPA 54, National

Fuel Gas Code

A vent shall not terminate directly above a sidewalk or paved driveway that is located be-

tween two single family dwellings and serves both dwellings

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides

beneath the floor

** Clearance in accordance with local installation codes and the requirements of the gas sup-

plier.