P40R-F I&O Manual
IM120801
RD: MAY 2014
RL: 3A

IMPORTANT: Single or multiple heater placement must be such that continuous

operation of heaters will not cause combustible material or materials in storage to

reach a temperature in excess of ambient (room) temperature plus 117F° (65C°).

It is the installer’s responsibility to ensure that building materials with a low

heat tolerance which may degrade at lower temperatures than the clearance

temperature are protected to prevent degradation.

Examples of low heat tolerance materials include vinyl siding, fabrics,

some plastics, filmy materials, etc.

Refer to “Clearance to Combustibles” information on pages 7 to 10, and Figure 1 and

Table 1, and listed on the heater rating plate (on burner housing).


MODEL

GUIDELINE *

MOUNTING

HEIGHT

ft (m)

MAXIMUM

BETWEEN

HEATERS

ft (m)

DISTANCE – HEATER LONG AXIS

PARALLEL TO WALL

HORIZONTAL

ft (m)

ANGLE MOUNTED

P40-R

8 – 18

(2.4 - 5.5)

20

(6)

5 – 12

(5 - 8)

MINIMUM: COMBUSTIBLE

CLEARANCE BEHIND

(refer to Table 1)

9. SUGGESTED GUIDELINES FOR HEATER PLACEMENT*

- SPACE HEATING APPLICATIONS

*

SUGGESTED GUIDELINE MOUNTING HEIGHTS are typical to provide optimum comfort in

general space heating applications. Variance from these typical heights can occur in some
applications:



Higher mounting height due to structure or application requirements



For ‘area’ or ‘spot’ heat, or in areas with greater infiltration rates (near overhead doors,

etc) where more intense heat is needed to provide better comfort then lower mounting

heights are recommended (minimum 8 ft [2.4 m] mounting height)



It is recommended that Protective Guard JS-0502-UR-GK be installed on any heater

mounted with less than 8 feet from floor to bottom of heater (See Accessories - Page 41)