Schwank compactSchwank P40-R User Manual

Page 23

Advertising
background image

23

P40R-F I&O Manual

IM120801

RD: MAY 2014

RL: 3A

V

ERTICAL

VENT

THROUGH

THE

ROOF

: (Horizontal vent through side wall is on pages 20

-

21)

It is the sole responsibility of the installer to adhere to all current local codes and/or ANSI
Z223.1 / CSA.B149.1 latest editions for all venting requirements, and practices.



Refer to General Venting Requirements on page 19



Any horizontal portion of vent must be mini-
mum 26 gauge single wall type “C” vent
pipe of 4” (10 cm) diameter (seal all con-
nections); vertical portion of vent can be 4”
type “B” vent



When the vent pipe passes through a cold
or unheated area where the ambient tem-
perature is likely to result in condensation
of the flue gases, the vent pipe will be
type ‘B’ vent or insulated with a suitable
material as approved and specified by the
insulation manufacturer to withstand tem-
perature up to 460°F (238°C).



Use an approved ‘B-vent’ termination cap
as supplied by the manufacturer of the
listed ‘B-vent’.



Minimum length of a vertical roof vent:



Minimum 12 inch (1 ft; 30.5 cm) single
wall ‘C’ vent



Plus one 90° “C” vent elbow



Plus minimum 36 inch (3 ft; 91.4 cm)
double wall ‘B’ vent



Total minimum linear vent length of 48
inches (4 ft; 122 cm) plus one 90° ‘C’
elbow



Maximum length of a vertical roof vent:



Above minimum requirements must be met



A maximum of one 90° elbow (equivalent 5 ft) plus two 45° elbows (each equivalent to
2.5 ft) can be installed in a vertical vent system



Refer to local and national codes for maximum allowable venting

Approved
Cap

Approved
‘B’ Vent

24”

60 cm

12

9

If roof slope exceeds 9:12
consult NFPA-54 ANSI
Z223.1 or CSA-B149.1

FIGURE 12

Up

to

Minimum 12”

(30.5 cm)

‘C’ Vent

Minimum 36”

(91.5 cm)
‘B’ Vent

90° ‘C’ Vent
Elbow

‘C’ to ‘B’ Adapter

Thimble

FIGURE 13