Schwank compactSchwank P40-R User Manual

Page 37

Advertising
background image

37

P40R-F I&O Manual

IM120801

RD: MAY 2014

RL: 3A

Maximum Power Flow = 21VA

24. CHANNEL MICRO 50N DSI WIRING DIAGRAM:

24V OR 120 VOLT THERMOSTAT - SINGLE HEATER PER THERMOSTAT

Each tube heater requires 120V, 60 HZ electrical power sized for 145VA. The heater includes
a 24V/120V relay switch . Maximum power draw for internal 24V burner components is 21VA.

The heater must be electrically grounded in accordance with the National Electrical Code.
ANSI / NFPA 70 or current Canadian Electrical code CSA C22.1.

A maximum night set-back of 9°F (5°C) is recommended for optimum economy and comfort.
To maintain satisfactory comfort levels do not turn off the heating system over night/weekends.