Clearance to Combustibles

Location of flammable or explosive objects, liquids or vapors close to the heater may cause fire

or explosion and result in property damage, injury or death. Do not use, store or locate flamma-

ble or explosive objects, liquids or vapors in the proximity of the heater.

The clearance to combustible material represents the minimum dis-

tance that must be maintained between the outer heater surface and

a nearby surface. The stated clearance to combustibles represents a

surface temperature of 117F° (65C°) above room temperature. It is

the installer’s responsibility to ensure that building materials with a

low heat tolerance which may degrade at lower temperatures are

protected to prevent degradation. Examples of low heat tolerance

materials include vinyl siding, fabrics, some plastics, filmy materi-

als, etc.

A peel and stick sign is included with this heater to specify the required clearances from the

heater to any combustible materials or vehicle. The sign must be posted either adjacent to the

heater thermostat or in the absence of such thermostat in a conspicuous location. In addition to

stored or stationary material, consideration must also be given to moveable objects such as ve-

hicles and overhead doors, and structural objects such as shelving, sprinkler heads, electrical

and gas lines, and electrical fixtures.

Do not store any combustible materials or install shelving or other projections within the

“Clearance to Combustibles” box - see Figure 1 and Table 1 on the next pages.

It is beyond the scope of these instructions to consider all conditions that may be encountered.

Consult local authorities such as the Fire Marshall, insurance carrier, or safety authorities if you

are uncertain as to the safety or applicability of the proposed installation.

Refer to Figure 1 and Table 1 in this manual, and/or the rating label affixed to the burner

housing for the certified clearances to combustibles for the heater.

WARNING

Gas Connection

Improper installation, connection, or adjustment can result in property

damage, toxic gases, asphyxiation, injury or death. The gas supply

must be connected and tested in accordance with all local, state, pro-

vincial, and national codes (ANSI Z223.1/NFPA 54 in USA; CSA B149.1 in Canada).

Refer to Section 13