Schwank ThermoControl Plus Series CM-485 User Manual

Page 16

Advertising
background image

- 16 -

0052h: Zone4 Frost protection value ×10 with sign
0054h: Zone5 Frost protection value ×10 with sign
0056h: Zone6 Frost protection value ×10 with sign
0058h: Zone7 Frost protection value ×10 with sign
005Ah: Zone8 Frost protection value ×10 with sign
*005Ch: Selected application program (P0, P1...) number. Here: 0,1,2,3,4,5
*005Eh: Number of Zones as configured. Max: 8 at this type.
*0060h: Error signals: in case of an error the corresponding bit: 1.

bit7

: Error relay is on (relay contacts closed)

bit6

: Sensor Error

bit2

: Button is stuck

bit1

: Alarm signal (contact input is opened)

bit0

: Battery is low (discharged)

*0062h: State of the contact inputs (a closed contact sets the bit to 1)

bit2

: “Error” (Störung) contact

bit1

: “Alarm” contact

bit0

: “Remote” contact

*0064h: Outside temperature ×10 with sign. Example: FFE2h –3.0°C

When ATF sensor is not connected: F830h (-200.0)

*0066h: bit3: State of the vent. Relay 7-8: 1 if relay is on (relay contacts closed).

bit2

: State of the vent. Relay 5-6: 1 if relay is on (relay contacts closed).

bit1

: State of the vent. Relay 3-4: 1 if relay is on (relay contacts closed).

bit0

: State of the vent. Relay 1-2: 1 if relay is on (relay contacts closed).

*0068h: State of Zone 1:

bit7

: 1 when Zone 1 is enabled (see: 000Ch)

bit6

: 1 when there is a sensor error in Zone 1

bit5

: 1 when “Error” (Störung) contact is closed

bit3

: 1 when Ventilator relay is on,

bit2

: 1 when heater is operated with full load (Stage 2) in Zone 1

bit1

: 1 when heater is operated with part load (Stage 1) in Zone 1

bit0

: 1 when selected control mode is 2-stage in Zone 1;

0 when selected control mode is 1-stage in Zone 1

*006Ah: State of Zone 2: format same as at Zone 1
*006Ch: State of Zone 3: format same as at Zone 1
*006Eh: State of Zone 4: format same as at Zone 1
*0070h: State of Zone 5: format same as at Zone 1
*0072h: State of Zone 6: format same as at Zone 1
*0074h: State of Zone 7: format same as at Zone 1
*0076h: State of Zone 8: format same as at Zone 1
*0078h: Zone1 Actual set value ×10 with sign, the controller presently tries to keep this

temperature value

*007Ah: Zone2 Actual set value ×10 with sign
*007Ch: Zone3 Actual set value ×10 with sign
*007Eh: Zone4 Actual set value ×10 with sign
*0080h: Zone5 Actual set value ×10 with sign
*0082h: Zone6 Actual set value ×10 with sign
*0084h: Zone7 Actual set value ×10 with sign
*0086h: Zone8 Actual set value ×10 with sign
*0088h: The measured and displayed room temperature ×10 with sign in Zone1
*008Ah: The measured and displayed room temperature ×10 with sign in Zone2