Register addresses:

The function of the registers in the Module depends on the type of the controller (TC+1,
TC+2, TC+4) in which the module is used. Detailed descriptions of the functions can be
found in the manuals of the different controllers. Here you can find the list of addresses at
the different types of controllers: See: TC+1 below; TC+2 page 12; TC+4 page 15

ThermoControl-Plus 1

*0000h: Hi: Controller type code (35h),

Lo: Version number.

0002h: No

function

0004h: Disable or enable buttons individually. Detailed in Appendix.
0006h: Simulation of pushing a button . Detailed in Appendix.
0008h: Special button combinations. Detailed in Appendix.
000Ah: Simulation of releasing a button.
000Ch: in Zone 1 control is enabled (On) or disabled (Off), 1: On, 0: Off
000Eh: in Zone 2 control is enabled (On) or disabled (Off), 1: On, 0: Off
0010h: No

function

0012h: No function
0014h: No

function

0016h: No function
0018h: No

function

001Ah: No function
001Ch: Set value type selection in Zone 1:

0000h:

Based on time program,

0001h: Frost

protection

value (continuously)

0002h:

Night value (continuously)

0003h:

Day value (continuously)

001Eh: Set value type selection in Zone 2: same as described at Zone 1
0020h: No

function

0022h: No

function

0024h: No function
0026h: No function
0028h: No

function.

002Ah: No function
002Ch: Zone1 Day set value ×10 with plus/minus sign.

Example: 00C7h 19.9°C

002Eh: Zone2 Day set value ×10 with plus/minus sign.
0030h: No

function

0032h: No

function

0034h: No

function

0036h: No

function

0038h: No

function

003Ah: No

function

003Ch: Zone1 Night set value ×10 with sign.
003Eh: Zone2 Night set value ×10 with sign.
0040h: No

function

0042h: No

function

0044h: No

function

The *-marked addresses are “Read-only” types