Error Caused

by

83h Month>12
84h

Too many days

85h Year<8,

Year>50

89h

A manual setting

is presently going

on at the unit

8Ah

Ending date is

earlier than

starting date

Reading out the holiday program

Load 0022h into register 0144h.

:02060144002292

As a result the data of the eight holiday programs will be loaded to register area 0144h-
0173h.
To read out the data of holiday program 1 from address 0144h :020301440003B4

In the answer we will get all data of holiday program 1:

:020306121203030808BB









Read out address 0174h :02030174000181

It will show which ones of the 8 programs are presently switched on (On/Off Mask):
:020302A00059

HOL.

1 2 3 4 5 6 7 8

80h 40h 20h 10h 8h 4h 2h 1h

On

x x


Writing the holiday program

Load the table (0144h – 0173h) with the necessary data in the following order: start day,
end day, start month, end month, start year, end year. Year must be given as 08 not
2008.
After this write into address 0174h the "On/Off Mask" (see above) and 41h.
Command 41h will start the writing procedure. :02060174A041A3

Then read out area 0174h – 0175h.

:02030174000186

In the answer we will get the On/Off Mask and the
possible errors.
:020302A00059

Error information

On/Off

Mask


If the value of the error is 0 the writing is carried
out.
Possible Error types and codes are listed here.

In

case of any error the writing of the good data will
also be prohibited. Data checking will be carried

out

only at the on-state programs.

Content Value
Start day

18

End day

18

Start month

03

End month

03

Start year

2008

End year

2008