Schwank ThermoControl Plus Series CM-485 User Manual

Page 20

Advertising
background image

- 20 -

bit2=1 Active
bit2=0 Inactive

[bit1-bit0]
01: Frost protection value
10: Night value
11 or 00: Day value

Time program registers overview

The table below contains the register addresses of the different time programs.
All the data of a time program is stored in two 16-bit registers.

Program Nr. Address

Program Nr. Address

1 00F6h

11 011Eh

2 00FAh

12 0122h

3 00FEh

13 0126h

4 0102h

14 012Ah

5 0106h

15 012Eh

6 010Ah

16 0132h

7 010Eh

17 0136h

8 0112h

18 013Ah

9 0116h

19 013Eh

10 011Ah

0142h 0143h

Zone Nr.

Command / Error


Zone Nr.:

Between 1..8 depending on the type of the controller

Commands:

22h: Load data of a certain Zone into the registers.

41h: Write content of the registers into a certain Zone.

Error:

See at chapter “Writing time program into a Zone”

Reading out a time program from a certain Zone

Load 0122h into register 0142h.

:02060142012293

Zone number (here:1)


After this the data of the 19 time programs on Zone 1 will be loaded to registers 00F6h-
0141h. Then the time programs can be read out one by one.
For example:
Reading out time program Nr.2 from address 00FAh

:020300FA0002FF

In the answer we will get all data of time program Nr.2:

:020304067C03CFA3


Hi

Lo Hi

Lo

Status + Value type

Group of days

Minute (0…1439)

06h

7Ch

03CFh

00000110b 01111100b

975

Active + Night value

Workdays

16 hour 15 minute






Monday Tuesday Wednesday Thursday Friday Saturday Sunday

1 1 1 1 1 0 0