- 7 -

The answer may be:

:020302810375

1 2 3 4 5 6 7 8 9 10

11 12 13 14 15

: Dev addr Status

Length

Data

LRC CR LF

:

02 03 02 81 03 75

0Dh

0Ah

Hi

Lo

The “Length” indicates that there will follow 2 byte. The 16-bit figures will arrive in
High-Low order.
Byte order of the 32-bit figures: (sample: 4byte work-hour counter)

Hi Lo Hi Lo 2x16bit

Hi Lo

32bit

Register writing

In this example we are writing “1” to address “2”.

:020600020001F5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

:

0 2 0 6 0 0 0 2 0 0 0 1 F 5

0Dh 0Ah


As an ASCII code:

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

3Ah 30h 32h 30h 36h 30h 30h 30h 32h 30h 30h 30h 31h 46h 35h 0Dh 0Ah


Structure:

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

: Dev addr fcode

Reg. address

Data

LRC

CR LF

Hi Lo Hi Lo

In the example the "Dev addr" is the unique number of the device.
The fcode=06 indicates the writing request.
The Reg.address gives the 16-bit address.

Data: contains the 16-bit data.
LRC, CR, LF: same as in case of reading.
Only one 16-bit register can be written at a time.

If there was no error, the answer will be the same as the order:

:020600020001F5