- 17 -

5 Set up the operating parameters


The “setup” switch as well as the jumper selection of the program P1 … P5 may only be
changed after the main power to the controller has been switched off. Before you open the
control unit read the important information in chapter 2!

The set up of operation parameters

can be modified from the front panel with the “setup” switch in the “On” position. Only a trained
and knowledgeable technician should modify the operating parameters

. After setting up the

operation parameters, turn off main power and switch the “setup” switch to the “Off” position to lock

the parameters.
To access the setup switch

: The switch permit setup: “ON”, locks the setup: “OFF”.

Switch off the main electrical supply before changing the switch position between

“On” and “Off”.

It is not sufficient to switch off the I/O switch on the front panel of the

controller, the external main switch must be switched off to avoid electric shock or possible

damage to the module.

Open the case cover door and loosen the four big plastic screws at the corners to release

the outer enclosure case.

Setup switch is located inside the outer enclosure case to the left side of the battery.




The application program is selected at the controller unit (P1, P2, P3, P4, P5). Perform this

operation with the main power supply switched of. Place the “jumper“ in the correct position. Only

one program can be selected at any one time. Double check that the jumper is positioned for the

correct application program!

If the application program is changed (jumper moved) after set up, all parameters switch back to

the default factory setting (chapter 5.1 and 5.2)!

P1 - Eight control circuits, single-stage

P2…P5 - Variations of control circuits - combines single- and two-stage zones

5.1 Enter the number of control zones

The controller is able to manage one or two control zones, depending on the chosen application. In

the following example the actual number of control zones are set.






Push the DISP button to return to the normal functions.

Hold the ZONE button for about 3

sec.. The number of available

control circuits appears in the

display (for example.: 1-8: four

control circuits). The desired

number of control circuits can be

selected by pushing +/- (1-7).

- All zones single-stage

- 1 zone 2-stage, up to 6 single-stage

- 2 zones 2-stage, up to 4 single-stage

- 3 zones 2-stage, up to 2 single-stage

- 4 zones 2-stage