6.12 Communication connection

Two types of optional communication cards can be used and connected to the "Communication"

terminal (only one type can be used at a time):

-CM485 card: Modbus (RS485) output, standard interface to building and industrial supervisory

systems. The output of this card is optically isolated from the controller.

-CM232 card: RS232 output, built-in 3-weeks data logger. Direct connection to telephone modem

or PC. Stored data can be downloaded to PC, remote setting of the controller from the PC.

The signal output ground of the CM232 module is directly connected to the controller's

common ground "COM". If the signal line of the connected computer is grounded, the

common ground "COM" of the controller will be grounded as well. This will change state

from isolated to grounded.

6.13 Common fault signal

In case of any operational error the red “ERROR” symbol starts to blink, simultaneously the error

relay switches on (connections 1, 2, 3). The display shows the affected control zone. Type and

cause of the problem is also indicated by other symbols displayed. To select another control zone

press “ZONE” - in doing so, the red “ERROR” signal won’t disappear, because the cause of the

problem is not yet solved. The blinking “ERROR“ signal and the activated error relay can be
deactivated by switching off the operational function of the zone using the

button.

Sensor error

: The temperature sens

or is not properly

connected. It is damaged or short-ci rcuited. Verify connections

and wires. In case of any sensor error the controller does not

switch off the heater zone (relay output is kept activated).

Battery error

: Battery low or discharged. Replace the battery

immediately. The battery is located inside the control unit cover.

Type: 1.5V (AA). Use long-life batteries. Before changing the

batteries please read the general se curity instructions – and in

particular Section 4.4.4!

Alarm signal

: Does not point out the kind of operational error.

It only shows that an error message has arrived at the “alarm

contact”. The controller swit ches off all heaters and exhaust

fans. If the “alarm contact” is not used the connections should

be bypassed.

This display is a very rare erro r: a forced position of a button at

the front panel. Please check!

This is an error message (opti on) of a heater (connections 72-

73). The operation mode of the controller is not changed due to

the error signal.