- 22 -

6.2 Sensor connections

The sensor is connected with two wires. The sensor does not require shielded cable, because the

controller includes effective protection. The l ength of wire up to 650 ft (200 m) does not influence

the accuracy of the temperature measurement. Do not run the s ensor lead next to high voltage

wires. The sensor connection must match the selected operating program (single- and/or two-stage

zones). Unused inputs must be kept free of usage!

6.3 Heater Connection

Only 24Vac Class 2 equipment can be connected to the controller!

The controller interior

relays switch 24Vac to the connection terminals (w et contact). Use 24Vac Class 2 rated power

relays to control heaters and ancillaries. Note that the total load is limited to 6.3 A.

6.4 Zone Configuration – Standard Tube Heaters (single firing rate)

Standard tube heater

zones can be set up as single-stage, or two-stage. Two-stage zones have a

proportion of the heaters on low-stage, with the balance of the heaters in the zone on high-stage.

Refer to sections 5 and 5.2. A zone can contain up to ten standard tube heaters. The location of

the jumper in P1 … P5 determines the quantity of single-stage and two-stage zones. Refer to

configuration diagram below and wiring diagram (8.1) for standard tube heaters.

Error Output

Eight relays supplied

! See Section 6.11

Jumper Pins are

located inside the

controller to the

right side of the

battery.
Jumper position

(P1 … P5)

determines the

zone strategy for

quantity of single-

DO NOT USE FAN

OUTPUTS

(SEE SECTION 5.2)

FAN OUTPUTS

FOR TWO-STAGE

LUMINOUS ONLY