5 zone configuration – two stage tube heaters – Schwank ThermoControl Plus 4 User Manual

Page 23

Advertising
background image

- 23 -

6.5 Zone Configuration – Two Stage Tube Heaters

For two-stage tube heaters

: All heater zones are set up as two-stage only. Pairs of controller

outputs control low and high fire. The location of the jumper in P5 establishes four two-stage

zones. A 100VA 120V/24V transformer is supplied to power the controller, and eight 24Vac

external relays are also supplied. Additional field supplied items required for EACH two-stage zone:

Qty 1 x 100 VA 120V/24V transformer; Qty 2 x external zone relays (one Low-stage + one High-

stage); Qty 2 per heater in zone x external heater relays (one Low-stage + one High-stage). Refer

to configuration diagram below and wiring diagram for two-stage tube heaters.

6.6 Zone Configuration – Luminous (high intensity) Heaters

A luminous heater has a 24Vac ignition control module and gas valve. While individual heaters are

single-stage, heater zones can be set up as single-stage, or two-stage. Two-stage zones have a

proportion of the heaters on low-stage, with the balance of the heaters in the zone on high-stage.

The quantity of luminous heaters in a zone is typically limited by: the dimensional size of the zone;

capacity of exhaust fan to satisfy the total input of the zone.
The location of the jumper in P1 … P5 determines the quantity of single-stage and two-stage

zones. For single stage zones, zone relays (eight supplied) switch line voltage to field supplied

exhaust fan and transformer in each zone. Heating zone required exhaust volume is:

USA: 4 cfm/1,000 Btuh input; Canada: 300 cfm/100,000 Btuh input. Zone transformer sizing: 40VA

first heater + 20VA each additional heater in zone.
The configuration diagrams below indicate the single- and two stage zone strategies for Jumper

positions P1 to P5. Also refer to the wiring diagram for luminous heaters.

Error Output

! See Section 6.11

Jumper Pins are

located inside the

controller to the

right side of the

battery.
Jumper position P5

establishes all two-

t

h t

DO NOT USE FAN

OUTPUTS

(SEE SECTION 5.2)

FAN OUTPUTS

FOR TWO-STAGE

LUMINOUS ONLY