Schwank ThermoControl Plus 4 User Manual

Page 18

Advertising
background image

- 18 -

5.2 Set up system operation parameters

To set up the parameters hold the
DISP

button for approximately 3

seconds. The “PAr” symbol appears

briefly. The operation parameters can

be selected with the SEL button.

Integration band

: Two-stage mode

only

: 0.5...3.0 °C / 1.0...5.5 ºF

In single-stage mode: (--.--) appears

Integration time

: Two-stage mode

only

: 10 … 99 minutes

In single-stage mode, or in off-state

(--.--) appears.

Hysteresis

, can be activated by

0.2 … 2.0 °C / 0.4...3.6 ºF

Sensor correction

: if the sensor

could not be mounted at the optimal

location, the meas ured temperature

can be revised:-9.9..+10.0 °C / -

9.9..+10.0 ºF

t1

: Heater starts and runs at full

power then stops at the programmed

time, in this case: 0…5 minute.

t2

: For the displayed time, the heater

stops completely (5..60 Sec). it only

appears, if the t1 doesn’t equal zero.

Minimum heater run time

: ( 0...15

min)

Ability of a restart:

t3

: Heater starts at full load for 1

minute, then the controller switches to

the regular mode (0: off). It does not

appear unless the two-stage control

is selected.

Override Duration

:

+h

(0:00-

24:00)