6 installation & configuration, 1 electrical supply – Schwank ThermoControl Plus 4 User Manual

Page 21

Advertising
background image

- 21 -

Door

Lock

Screw

Upper part

Lower part

Bracket

244

265

180

205

25

140

96

6 Installation & Configuration

6.1 Electrical Supply

The controller must be electr ically grounded in accordance with the National Electrical

Code. ANSI / NFPA 70 or current Canadian Electrical code CSA C22.1.

Appliance and control wiring must be in accordance with all applicable local codes.

The controller must be isolated from the main power supply during installation or
connection work is carried out!

The "Off" position (O) of the controller I/O switch

does not provide complete isolation of the controller!

The controller power supply connection terminals are identified as "L

24V

"

and "COM". The "COM"

connection point is the common ground in the circuit: it is directly connected to the points of the

relay outputs marked "C", and it is the common

point of the signal input terminals and the

communication terminal. The "L

24V

" power supply is connected th rough a Fuse (6.3A) to the

connection terminal "L1". It is important to make connections correctly in accordance with the
wiring schemes of the selected application program!







Pay special attention to common ground when

connecting outside devices so that a short-circuit does

not occur.

If several ThermoControl units are connected to one

24VAC power supply, ensure to connect the same

terminals of the power supply to the "L

24V

" and "COM"

terminals of the controllers.