Schwank ThermoControl Plus 4 User Manual
Page 26
- 26 -
6.6.3 Zone Configuration – Luminous (high intensity) Heaters
JUMPER IN POSITION 3 (P3): Two two-stage zones + up to four single-stage zones
The jumper pins P1 to P5 are located inside the controller cover to the right side of the battery. The
location of the jumper in P1 … P5 determines the quantity of single-stage and two-stage zones.
With the jumper in position P3, two zones are two-stage, and the balance of the zones are single
stage. Eight relay switches are supplied with the controller to switch line voltage to the zone
exhaust fans (field supplied) and to the zone transformers (field supplied). Two additional field
supplied relay switches (P/N: JS-0568-CC) are required to power the exhaust fans for the two-
stage zones.
The fans for the two-stage zones are controlled by the controller fan outputs 10-11 and 12-13.
Fans for the single-stage zones are controlled by the heater outputs 28-35. Single-stage zone
exhaust fans are wired in parallel to the heater zone transformer.
The 120V/24Vac zone transformer is ‘sized’ to provide sufficient power to all heaters in the zone:
40VA for first heater + 20 VA for each additional heater. A separate transformer is required for
each of the Low- and High-stage zones in two-stage Zones 1 and 2.
Refer to the diagram below, and the wiring diagram “Luminous Heaters – Two-Stage Zone”.
USE FAN
OUTPUTS
FOR TWO-
STAGE
ZONES
ONLY
Only use fan outputs
for two-stage zone(s)*
Error Output
! See Section 6.11 !
Jumper Pins are located
inside the controller to the
right side of the battery
Eight relays
supplied
Zone exhaust fans
(field supplied)
Additional relays for fans (field supplied)