6.6.2 Zone Configuration – Luminous (high intensity) Heaters

JUMPER IN POSITION 2 (P2): One two-stage zones + up to six single-stage zones
The jumper pins P1 to P5 are located inside the controller cover to the right side of the battery. The

location of the jumper in P1 … P5 determines the quantity of single-stage and two-stage zones.
With the jumper in position P2, one zone is two-stage, and the balance of the zones are single

stage. Eight relay switches are supplied with the controller to switch line voltage to the zone

exhaust fans (field supplied) and to the zone transformers (field supplied). One additional field

supplied relay switch (P/N: JS-0568-CC) is required to power the exhaust fan for the two-stage

zone.
The fan for the two-stage zone is controlled by the controller fan outputs 10-11. Fans for the single-

stage zones are controlled by the heater outputs 24-35. Single-stage zone exhaust fans are wired

in parallel to the heater zone transformer.
The 120V/24Vac zone transformer is ‘sized’ to provide sufficient power to all heaters in the zone:

40VA for first heater + 20 VA for each additional heater. A separate transformer is required for

each of the Low- and High-stage zones in two-stage Zone 1.
Refer to the diagram below, and the wiring diagram “Luminous Heaters – Two-Stage Zone”.

USE FAN

OUTPUTS

FOR TWO-

STAGE ZONE

ONLY

Only use fan outputs

for two-stage zone(s)*

Error Output

! See Section 6.11 !

Jumper Pins are located

inside the controller to the

right side of the battery

Eight relays

supplied

Zone exhaust fans

(field supplied)

Additional relay for fan (field supplied)