Rockwell Automation 20P PowerFlex DC Drive - Frame D Bimetal Thermostat User Manual
Page 5
![background image](/manuals/576796/5/background.png)
5
Important: Note the terminal number on the fuse switch to which the signal
wires are connected for proper re-installation.
4. Remove the signal wires from the fuse switch connectors and secure the
wires in a position above the input terminals.
5. Loosen the lower bolt and washer that secures the bottom of the leg fuse to
the Phase U SCR module leg input terminal.
6. Loosen the upper bolt and washer that secures the top of the fuse to the AC
input terminal, rotate the top of the fuse out and downward, and remove the
fuse from the lower terminal.
1
4
2
Phase U SCR module
leg input terminal
Phase U AC
input terminal
Loosen upper bolt
Loosen lower bolt
Remove wires
from switch
Rotate top of fuse
downward and lift
off lower terminal
Note the terminal number on the
fuse switch to which the signal
wires are connected.