Drive Coolant Requirements

Table 1.A

lists approved sources and recommended coolants with

appropriate corrosion inhibitors

for the drive loop:

Non-diluted coolants require a coolant-to-water mix ratio of 50% by
volume.

Table 1.B

lists the estimated amount of coolant needed for the drive

loop based on the drive frame size.

Important: Since coolant performance slowly degrades over time, the drive

loop coolant should be replaced every two years and/or
whenever the loop is drained for servicing. See

Draining

Coolant from the Drive Loop for Periodic Replacement on
page 2-5

for instructions.

If an approved coolant is not used, the drive coolant must consist of clean
water with a corrosion inhibitor. An approved corrosion inhibitor is
Chemtool, Inc. (www.chemtool.com) part number Watertool 4435-C. The
recommended concentration of the inhibitor is 8-10% by volume. Deionized
water is prohibited. Use distilled water or water with less than 50 ppm
concentrations of:

• Sulfate and chloride

• Hard water ions such as Mg++ and Ca++

Table 1.A Recommended Drive Loop Coolants

Source

Coolant

Interstate Chemical

http://www.interstatechemical.com/

contact.htm

• NFP-50

(1)

; a 50/50 premix of propylene glycol and

distilled water

• NFE-50

(1)

; a 50/50 premix of ethylene glycol and

distilled water

(1)

Available in 5 gallon pails.

Koolant Koolers/Dimplex Thermal
Solutions

http://www.koolantkoolers.com/

index.php/nic=contact

• K-Kool-E

(1)

; ethylene glycol (available premixed with

distilled water)

• Propylene glycol

(1)

also available

Dow Chemical

http://www.dow.com

• Dowtherm

®

SR-1

(2)

; ethylene glycol

• Dowfrost

®

(2)

; propylene glycol

Dowtherm and Dowfrost are registered trademarks of the
Dow Chemical Company

(2)

Not premixed with distilled water, and may not be available in 5 gallon quantities.

Table 1.B Estimated Coolant Amount for the Drive Loop

Drive Size

Estimated Amount of Coolant

(1)

(1)

The estimated amount of coolant is based on the heat exchanger using 1.2 m
(4 ft.) hoses. Longer hoses require more coolant. The maximum hose length
of 9.1 m (30 ft.) would require up to an additional 2.8 liters (3/4 gal.).

Frame 2

15.1 liters (4 gal.)

Frame 3A

19 liters (5 gal.)

Frame 3B

19 liters (5 gal.)