Heat Exchanger Schematic

B-3

PowerFlex 700L Liquid-to-Liquid Heat Exchanger User Manual

Publication 20L-UM002A-EN-P

Pump Wiring 115V

Motor:
Emerson SFE06821S
60Hz 50Hz
1.0 HP 1.0
3450 RPM 2850
115/208-230 Volts 220-230
12.2 / 6.4-6.1 FLA 7.3-7.7

Pump:
Goulds Pump, ITT
Series MCS Size 1x 1 1/4-6
Cat. No. 1MS1E4D4 Impeller Dia. 4-3/4

NOTE: Default factory wiring is for operation at 115VAC, 60Hz.

GND

Blue

Yellow
White

Brown
Orange

15

17

16

19

18

16 AWG Red

16 AWG Red

Fault Contact

Field Installation

(Supplied by Drive)

Alarm Contact

Interlock Contact

16 AWG

16 AWG
16 AWG
16 AWG

COM

16 AWG

N.C.

16 AWG
16 AWG

COM
N.O.

16 AWG
16 AWG

COM
N.O.

1
2

1

S1

STATUS

POWER

S2

2

3
4
5

1

F1

2
3
4
5

6
7
8
9

10

0.5A 250V

Type 3AG Fuse

Field Installation

Remote Start Contact

Low Voltage

(Supplied by Frame 2 Drive)

Field Installation

Remote Start Contact

High Voltage

(Supplied by Frame 3A or 3B Drive)

181052-A01

Cooling Loop

Control Board

112PB

Prime Switch

20
21
22
23

25

24

+12 VDC

To

TB1

(1b-5)

To

TB1

(1b-6)

To

Con

ver

ter

TB5-3

To

Con

ver

ter

TB5-1

12V Common

Neutr

al

Run

1
2
3
4
5
6
7
8

J5

J6

J7

J8

J3

J1

J2

11
10

9
8
7
6
5
4
3
2
1

Pump Wiring 230V

GND

Blue

Brown
Yellow

White
Orange

See

Setting the DIP

Switches on page 1-14

for

S1 and S2 switch settings.

See

Figure 1.7 on page 1-11

for 115 or 230 VAC operation
J2 jumper settings.