Power wiring, Power wiring -10 – Rockwell Automation 20L-LL PowerFlex 700L Liquid-to-Liquid Heat Exchanger User Manual

Page 20

Advertising
background image

1-10

Installation

PowerFlex 700L Liquid-to-Liquid Heat Exchanger User Manual

Publication 20L-UM002A-EN-P

Power Wiring

Connect line power to the power terminal block’s L1, N, and PE terminals
(

Figure 1.6

). Refer to

Table 1.E

for power terminal specifications.

Important: The heat exchanger is configured and shipped for 120 VAC

operation. However, its configuration can be changed to
operate on 230 VAC. For details, see

Configuring for 230 VAC

Operation on page 1-10

.

Table 1.E Power Terminal Specifications

Figure 1.6 Power Terminal Block Electrical Connections

Configuring for 230 VAC Operation

1. Open the cover of the electrical box (

Figure 1.1

) and set the J2 jumper on

the control board (

Figure 1.7

) to the 230 VAC position (terminals 1-7).

2. On the power terminal block (

Figure 1.6

), disconnect wire #3 from

terminal H2 and reconnect it to terminal H4 for 230 VAC operation.

3. Remove the heat exchanger’s top panel first and then its left side panel to

access the pump motor conduit box. Remove the conduit box cover and
change the motor winding connections for 230 VAC operation as shown
in

Figure 1.8

.

Name

Description

Wire Size Range

(1)

Recommended
Tightening
Torque (+10%)

Wire Strip
Length

Maximum

Minimum

Input Power Terminals —
PE, N, and L1

Input AC line power

3.3 mm

2

(#12 AWG)

0.05 mm

2

(#30 AWG)

N/A
(Spring-Loaded)

10 mm
(0.4 in.)

(1)

Maximum/minimum sizes that the terminals will accept - these are not recommendations.

J2

J1

J5

J6

J7

J8

L1

N

H1

H2

H4

PE

PE

Wire #3

(115 VAC Line

Power Connection)

Wire #3
(230 VAC Line
Power Connection)