Installation

1-13

PowerFlex 700L Liquid-to-Liquid Heat Exchanger User Manual

Publication 20L-UM002A-EN-P

Control Interlock Wiring

The interlock contact output on the heat exchanger control board can be
interlocked (

Figure 1.10

or

Figure 1.11

) with the PowerFlex 700L drive to

prevent the drive from running when the heat exchanger is in a faulted state.

Figure 1.10 Control Interlock Wiring for Drive with PowerFlex 700 Vector Control

Figure 1.11 Control Interlock Wiring for Drive with PowerFlex 700S Phase II Control

J2

J1

J1

J3

S1

S2

J4

J8

J7

J6

J5

FU1

1

9

1

5

1

2

3

4

5

6

7

8

9

10

1

10

1

8

11

1

2

3

4

5

6

7

8

9

10

11

24

Run

25
26
27
28

2-Wire Control

Non-Reversing

24V DC Internal Supply

Required PowerFlex 700 Vector
Control Parameter Changes:
P190 - [Direction Mode] = “0” (Unipolar)
P361 - [Digital In1 Sel] = “0” (Not Used)
P362 - [Digital In2 Sel] = “7” (Run)

Required PowerFlex 700 Vector
Control Parameter Changes: None

PowerFlex 700 Vector Control

Cassette I/O Terminal Block

Heat Exchanger

Interlock Contact

(30 VDC @ 10A Max.)

J1

Heat Exchanger

Interlock Contact

(30 VDC @ 10A Max.)

PowerFlex 700 Vector Control

Cassette I/O Terminal Block

1

2

3

4

5

6

7

8

9

10

11

24

Start

25
26
27
28

3-Wire Control Internal Supply

Stop

Heat Exchanger

Control Board

J2

J1

J3

S1

S2

J4

J8

J7

J6

J5

FU1

1

9

1

5

1

2

3

4

5

6

7

8

9

10

1

10

1

8

11

1

2

3

4

5

6

7

8

9

10

11

9

Run

10
11
12
13
14
15
16

2-Wire Control

24V DC Internal Supply

Required PowerFlex 700S Ph. II
Control Parameter Changes:
P829 - [Dig In5 Sel] = “7” (Run)

Required PowerFlex 700S Ph. II
Control Parameter Changes:
P828 - [Dig In4 Sel] = “5” (Start)
P829 - [Dig In5 Sel] = “14” (Normal Stop)

PowerFlex 700S Ph. II

Control Cassette TB2

1
2
3

1

2

3

4

5

6

7

8

9

10

11

Start

3-Wire Control Internal Supply

Stop

J1

Heat Exchanger

Interlock Contact

(30 VDC @ 10A Max.)

J1

Heat Exchanger

Interlock Contact

(30 VDC @ 10A Max.)

9

10
11
12
13
14
15
16

PowerFlex 700S Ph. II

Control Cassette TB2

1
2
3

Heat Exchanger

Control Board

Advertising