Rockwell Automation 56AMXN ControlLogix/AutoMax/Communication/Module User Manual
Page 13
 
DCSNet/RE RIO Module
13
Publication 56AMXN-IN002A-EN-P November 2002
Wire the Connector for the AutoMax Network
Use a drop cable, 612574-36R, available through Rockwell Automation Systems 
Business, and passive tap M/N 57C380 to connect the module to the coaxial 
network cable. This cable turns down and has a ferrite to reduce EMI. This cable 
must be used in CE applications. You can also use drop cable 612403-036R but it 
points up. 
The drop cable is a 3-foot long multi-conductor cable with 9-pin D-shell connectors 
at each end. Connect one end to the connector on the module and the other end to 
the passive tap. 
The passive tap has two BNC connectors for connection to the coaxial cables and 
terminating loads. 
The network coaxial cable must be terminated with 75 ohm terminating loads 
attached to the taps at the physical ends of the network. There should be two and 
only two terminators on the network. 
For DCS, the network cable can be RG-59/U or RG-11/U. For remote I/O, the 
cable must be RG-59/U.
Apply Chassis Power
Turn the rack power supply on.