DCSNet/RE RIO Module

15

Publication 56AMXN-IN002A-EN-P November 2002

Interpreting the Alphanumeric Display

The 56AMXN/B module displays alphanumeric messages that provide diagnostic
information about your module. The alphanumeric display displays warning

messages twice, then resumes the normal display. The following table summarizes
the messages.

Message Description

56AMXN Ver x.xx.xx

The module’s firmware version, displayed at
powerup.

Error: Heard Another DCS
Master

The module is configured as a DCS master and has
heard another DCS master on the network.

DCS Master

The module is a DCS master. Displayed during
normal operation.

Drop xx OffLine

DCS drop xx has gone offline.

DCS Slave Invalid Depth 0

The drop number switches are set for a drop number
from 1 to 55 but the drop depth switches are set to 0.

DCS Slave Drop+Depth 'xx'
Too High

The combination of drop number and drop depth
results in invalid drop numbers (>55). Check the
switch settings.

DCS Slave Drop=xx
Depth=xx Waiting...

The module is configured as a DCS slave with the
drop number and depth displayed, but is not
currently being scanned by a DCS master.

Error: Heard Duplicate DCS
Slave Drop xx

The module is configured as a DCS slave and has
heard a drop on the network with a drop number that
overlaps one of its active drops.

DCS Slave Drop=xx
Depth=xx

The module is configured as a DCS slave, with the
drop number and drop depth shown. Displayed
during normal operation.

Drop xx Timeout

DCS drop xx has timed out.

Mon Drop xx Timeout

Monitored DCS drop xx has timed out.

Firmware Update...

The firmware on the module is being updated.